General specifications |
Switching function | Normally closed (NC) |
Output Type | NAMUR |
Rated operating distance | 15 mm |
Installation | not flush |
Guaranteed operating distance | 0 ... 12.15 mm |
Reduction factor r Al | 0.4 0.4 |
Reduction factor r Cu | 0,3 |
Reduction factor r 304 | 0,85 |
Output Type | 2 threads |
Nominal ratings |
Nominal voltage | 8.2 V (R i approx. 1 kΩ) |
Frequency of change | 0 ... 100 Hz |
Current consumption |
Measuring plate not detected | min. 3 mA |
Measuring plate detected | ≤ 1 mA |
Parameters related to functional safety. |
MTTF d | 5070 to |
Mission Time (T M ) | 20 to |
Diagnostic Coverage (DC) | 0% |
Compliance with standards and directives. |
Standard Compliance |
NAMUR | IN 60947-5-6: 2000 IEC 60947-5-6: 1999 |
Standards | IN 60947-5-2: 2007 IN 60947-5-2 / A1: 2012 IEC 60947-5-2: 2007 IEC 60947-5-2 AMD 1:2012 |
Approvals and certificates |
EAC Compliance | TR CU 012/2011 |
UL Approval | cULus Listing, General Purpose |
CSA Approval | cCSAus listed, general purpose |
CCC Approval | No CCC approval/marking required for products classified ≤36 V |
Environmental conditions |
Ambient temperature | -25 ... 100 ° C (-13 ... 212°F) |
Mechanical specifications |
Type of connection | Terminal compartment |
Cross section of the nucleus | up to 2.5 mm 2 |
Housing material | PBT |
Sensitive face | PBT |
Degree of protection | IP67 |